BUILDING LEAKAGE TEST HPD Building Compliance Ltd Cherry Tree House High Street Thorndon, Suffolk IP23 7LX Phone: 01379 678092
Date of Test: 20th April 2015 Test File: Plot F21 Union Road, Clapham
Technician: David Taylor (BINDT Reg. 0276)
Customer:
Building Address:
Durkan Ltd 4 Elstree Gate Elstree Way Borehamwood, Herts WD6 1JD Phone: 020 8616 9700 Fax: 020 8619 9800
Test Results at 50 Pascals: V50: Airflow (m³/h) n50: Air Changes per Hour (1/h) w50: q50: m³/(h*m² Surface Area)
Block A, Third floor, Type A2 Flat F21, Flat 8 Union Road Clapham, London SW4 6JP
419 ( +/- 0.6 %)
2.82
Leakage Areas:
165.9 cm² ( +/- 3.6 %) Canadian EqLA @ 10 Pa or 1.11 cm²/m² Surface Area 88.6 cm² ( +/- 5.7 %) LBL ELA @ 4 Pa or 0.60 cm²/m² Surface Area
Building Leakage Curve:
Air Flow Coefficient (Cenv) = 33.5 ( +/- 8.9 %) Air Leakage Coefficient (CL) = 33.7 ( +/- 8.9 %) Exponent (n) = 0.645 ( +/- 0.023 ) Correlation Coefficient = 0.99556
Test Standard: Type of Test Method: Equipment:
EN 13829 Test Mode: Depressurization B Regulation complied with: ADL1A 2010 Model 3 Minneapolis Blower Door, S/N 11812
Inside Temperature: Outside Temperature: Barometric Pressure: Wind Class: Building Wind Exposure: Type of Heating: Type of Air Conditioning: Type of Ventilation:
18 °C 15 °C 101325 Pa 3 Gentle Breeze Partly Exposed Building Wet Rads
Volume: Surface Area: Floor Area: Uncertainty of Building Dimensions: Year of Construction:
149 m²
2% 2015
Central Extract
600 500 400 Building Leakage (m³/h)
300 200
100 90 80 4
5
6
7 8 9 10
20 30 Building Pressure (Pa)
40
50 60 70 80
BUILDING LEAKAGE TEST Page 2 Date of Test: 20th April 2015 Test File: Plot F21 Union Road, Clapham Comments Third floor flat wet Rads Temp seals to Central Extract registers Water in all traps DAP 3.0 Data Points: Depressurization Nominal Building Fan Pressure Pressure (Pa) (Pa) -0.1 n/a -64.9 28.6 -55.5 155.4 -55.2 156.6 -49.7 136.4 -45.5 122.9 -40.3 106.3 -34.4 91.4 -30.0 76.6 -24.9 60.9 0.1 n/a Test 1 Baseline (Pa):
Nominal Flow (m³/h)
Temperature Adjusted Flow (m³/h)
% Error
514 445 446 415 393 365 337 308 273
510 441 443 412 390 362 335 305 271
2.7 -1.7 -0.9 -1.4 -1.2 -0.8 1.4 1.1 1.2
p01- = -0.2
p01+ = 0.1
p02- = -0.2
p02+ = 0.2
Fan Configuration Ring B Ring C Ring C Ring C Ring C Ring C Ring C Ring C Ring C