MOTOR CIRCUIT PROTECTION FUSE-LINKS 400/415 Volt Industrial Fuse-Links with Bo l ted Co n n e ctions to BS88: Part 2 • IEC60269-2 • EN60269-2 Rated voltage: 415V a.c. Breaking range and utilization category: gM Rated breaking capacity: 80kA at 415V a.c.
To avoid nuisance fuse-link ope ration due to ove rcurrent starting surges, fuse-links used in motor circuits often require higher ratings than the full load current of the motor. Motor circuit protection fuse-links have a dual current rating, consisting of a continuous current rating and a rating r elating to the operational characteristics. The letter ‘M’ separates these two ratings, for example, 32M50. This represents a fuse-link with a maximum co ntinuous curre nt rating of 32 Am p s, and an operational characteristic of 50 Amps rating to meet the motor starting current. The
table
be l ow shows
the
recommended fuse-links for various sizes of three phase 415V a.c. induction motors, where the run-up time is less than five seconds and the starting duty infrequent, ie; not more than twice per hour. For more arduous conditions the next higher rating should be used.
* Non-Standardized current rating additional to BS 88: Part 2 This data is based upon normal conditions and average efficiencies and power factors. Conditions such as long run-up times, large numbers of starts in succession, high ambient temperatures or abnormal transients during star/delta switching may necessitate adjustments to fuse-link selection.
For detailed dimensioned outline drawings see pages 5 & 8
10
PRODUCT DETAIL AND PERFORMANCE DATA Product detail - Dual Rated Fuse-Links - Offset Tag List Reference NIT TIA TIS TCP TCP TFP
Current Rating (A)
BS88 Reference
20M25,20M32 A1 32M40,32M50,32M63 A2 63M80,63M100,100M125 A3 100M125,100M160 A4 100M200 A4 200M250,200M315 (as A4)
Voltage Rating (V)
415a.c.
Breaking Capacity (kA)
80kA-a.c.
BS Standard
BS88: Part 2
IEC Standard
60269-2
Carton Quantity
Carton Weight (Kg)
10 10 10 5 5 1
0.13 0.54 0.70 0.82 0.82 0.24
Carton Quantity
Carton Weight (Kg)
10 10 5 5 1 1 1 1
0.72 0.72 0.85 0.85 0.24 0.43 0.55 0.74
Product detail - Dual Rated Fuse-Links - Central Tag List Reference TB TBC TC TC TF TKF TMF TM
Current Rating (A)
BS88 Reference
63M80,63M100 63M80,63M100 100M125,100M160 100M200 200M250,200M315 315M400 400M500 400M500
(as B1) B1 B1 B2 B3 B4 C1
Voltage Rating (V)
415a.c..
Breaking Capacity (kA)
80kA-a.c..
BS Standard
BS88: Part 2
IEC Standard
60269-2
Product detail - Dual Rated Fuse-Links - Compact Dimension List Reference NS NS
Current Rating (A) 20M25, 20M32 32M40,32M50,32M63
BS88 Reference
Voltage Rating (V)
Breaking Capacity (kA)
BS Standard
IEC Standard
Carton Quantity
Carton Weight (Kg)
F1 -
415a.c.
80kA-a.c.
BS88: Part 6
60269-2
10 10
0.18 0.32
Performance Data - Dual Rated Fuse-Links - Offset Tag
Perf o r m a n ceData - Dual Rated Fuse-Links - Ce n t ral Tag
List Reference
List Reference
Current Rating (A) Cont Motor
BS88 Reference
Utilization Category
Current Rating (A) Cont Motor
BS88 Reference
NIT
20
25
A1
TB
63
80
-
NIT TIA TIA TIA TIS TIS TIS TCP TCP TCP TFP TFP
20 32 32 32 63 63 100 100 100 100 200 200
32 40 50 63 80 100 125 125 160 200 250 315
A1 A2 A2 A2 A3 A3 A3 A4 A4 A4 (as A4) (as A4)
TB TBC TBC TC TC TC TF TF TKF TMF TM
63 63 63 100 100 100 200 200 315 400 400
100 80 100 125 160 200 250 315 400 500 500
(asB1) (asB1) B1 B1 B1 B2 B2 B3 B4 C1
gM
Utilization Category
gM
Performance Data - Dual Rated Fuse-Links - Compact Dimension List Reference NS NS NS NS NS
Current Rating (A) Cont Motor 20 20 32 32 32
25 32 40 50 63
BS88 Reference
Utilization Category
F1 F1 -
gM
NOTE: Cont= Continuous Current. Motor = Motor Starting Current
See pages 22,23 & 25 for the time/current and cut-off current characteristics.
11