32pp Lv Fuse-links 2004


[PDF]32pp Lv Fuse-links 2004 - Rackcdn.comhttps://04646a9cf351cc0d3888-b8b406d15fe93f790abb5bf0e9ab7ab3.ssl.cf3.rackcd...

2 downloads 127 Views 269KB Size

CYLINDRICAL FUSE-LINKS

TYPE LPV

400/500/660 Volt Cylindrical Fuse-Links to IEC60269-2 Rated voltages: 400V a.c. , 500V a.c., 660V a.c. Bre a king range and utilization category: gG/aM/aR Rated breaking capacities: 20kA a.c., 80kA a.c., 120kA a.c. Voltage and current ratings and principal dimensions Voltage Breaking Current

List References

Principal Dimensions (mm)

Rating Capacity Rating (V a.c.) (kA) (A)

Standard

Indicator

Striker

L

D

400

20

1,2,4,6,8,10,12,16,20,25

LPVG8

LPVG8I



31

8

500

120

1,2,4,6,8,10,12,16,20,25,32

LPVG10

LPVG10I



38

10

660

80

1,2,4,6,8,10,12,16,20,25

LPVG14

LPVG14I LPVG14S

51

14

500

120

32,40

400

120

50 LPVG22I LPVG22S

58

22

660

80

4,6,8,10,12,16,20,25,32,40,50,63,80 LPVG22

500

120

100

400

120

125

Lawson Type“LPV”fuse-links with cylindrical bodies and ferrule end caps are used widely in

both

co m m e rcial

a p p l i cations.

and

industrial

Cylindrical fuse-links are

approved to IEC 60269, and are available in both gG and aM operating categories. A complementary range of solid/neutral links is available to suit our fuse-link ra n g e.

Note: 1. A range of fuse-links for motor circuit protection is available, substitute M for G in list references. 2. Fuse-links for semi-conductor protection and a range of fuse-holders, together with accessories, are also available.

GENERAL PURPOSE FUSE-LINKS

TYPE MD

400/415 Volt Ge n e ral Pu rpose Fuse-Links to BS88: Part 1 • IEC60269-1 Rated voltages: 415V a.c., 250V d.c. Breaking range and utilization category: gG Rated breaking capacities: 80kA at 415V a.c., 40kA at 250V d.c. Cu r rent ratings and principal dimensions

L awson Ty pe “M D” cylindrical fuse-links are for general purpose usage in three-phase sub-circuits. With a bre a king ca p a c i ty of 80kA, ty pe “M D”fuse-links can be used to pro tect circuits with high fault levels such as industrial installat i o n s. The fuse-links also meet the pe rfo rm a n ce require m e nts of BS88: Part 2 and IEC 60269-2 and have been indepe n d e nt l y ASTA Ce rtified to the rules of the ASTA 20 Scheme. 20

Cu rre nt Rating (A)

List Re fe re n ce

2 4 6 8 10 16 20 25 32

MD2 MD4 MD6 MD8 MD10 MD16 MD20 MD25 MD32

Principal Dimensions L mm

D mm

29

12.7

Ca rto n

Carton

Qu a nt i ty

Weight (Kg )

10