Customer Name: Project Name: Fixture Type: GENERAL CHARACTERISTICS Application Category Ballast Type

74472 - GE240RS-MV-N GE LFL Multi-Volt ProLine™ Electronic Program / Rapid Start Ballast • High performance electronic ballast for all general fluorescent applications • Multi-Voltage Technology handles voltage from 120 to 277V • Light-weight, Low Profile Housing • Parallel lamp operation means system maintenance is easier to manage

Starting Method Lamp Wiring Line Voltage Regulation (+/-) Case Temperature Ballast Factor Power Factor Correction Sound Rating Enclosure Type Additional Info Primary Application

2 or 1- F40 or F34T12 Rapid Start 120 to 277 "N" BF Linear Fluorescent Electronic - Program / Rapid Start Rapid start Parallel 10 % 70 °C(158 °F) Normal Active A (20-24 decibels) Metal Auto-restart/Thermally protected Standard

PRODUCT INFORMATION Product Code Description Standard Package Standard Package GTIN Standard Package Quantity Sales Unit No Of Items Per Sales Unit No Of Items Per Standard Package UPC

74472 GE240RS-MV-N Case 10043168744727 10 Standard Pack 1 10 043168744720

DIMENSIONS Case dimensions Length (L) Width (W) Height (H) Mounting dimensions Mount Length (M) Mount Width (X or F) Mount Slots (MS) Weight Exit Type Remote Mounting Distance to Lamp Remote Mounting Wire Gauge Lead lengths Qty Yellow 2 Blue 2 Red 2 Red 1 Black 1 Yellow 1 White 1 Blue 1

9.5 in(241.30 mm) 1.3 in(33.02 mm) 1.2 in(29.97 mm) 8.9 in(226.06 mm) 1.1 in(27.94 mm) 0.3 in(7.62 mm) 1.06 lb Side 18 ft 18 AWG Exit Right Right Right Right Left Right Left Right

Length (± 1 in.) 48.0 (1219mm) 33.0 (838mm) 33.0 (838mm) 33.0 (838mm) 25.0 (635mm) 48.0 (1219mm) 25.0 (635mm) 33.0 (838mm)

ELECTRICAL CHARACTERISTICS Supply Current Frequency

60 Hz

SAFETY & PERFORMANCE • • • • • • • •

cUL Listed NRCan UL Class P UL Listed UL Type 1 Outdoor UL Type HL RoHs Compliant FCC Part 18 Class B at 120 volts

SPECIFICATIONS BY LAMP & WATTAGE Lamp

F40T12 F40T12

# of Lamps Line Volts

1 1

120 277

System Watts

Nom. Line Current

48 48

0.41 A 0.19 A

For additional information, visit www.gelighting.com

System Ballast Factor

Ballast Efficacy Factor

Power Crest Factor THD% (<=) Factor% (>=) (<=)

Min. Starting Temp (°F/°C)

99 95

50.0 / 10 50.0 / 10

1.7 1.7

7 10

Page 1

F40T12 F40T12 F40T10 F40T10 F40T10 F40T10 F34T12 F34T12 F34T12 F34T12 F30T12/WM F30T12/WM F30T12/WM F30T12/WM F30T12 F30T12 F30T12 F30T12 F20T12 F20T12 F20T12 F20T12

2 2 1 1 2 2 1 1 2 2 1 1 2 2 1 1 2 2 1 1 2 2

120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277

74 73 42 42 75 72 41 41 63 62 30 30 50 50 37 37 60 58 28 29 46 45

0.67 A 0.3 A 0.35 A 0.17 A 0.63 A 0.27 A 0.35 A 0.17 A 0.56 A 0.26 A 0.26 A 0.13 A 0.42 A 0.2 A 0.31 A 0.16 A 0.31 A 0.22 A 0.24 A 0.13 A 0.39 A 0.18 A

0.89 0.89

1.20 1.22

0.88 0.88

1.17 1.22

0.87 0.87

1.38 1.40

0.95 0.95

1.90 1.90

0.95 0.95

1.58 1.64

1.00 1.00

2.17 2.22

99 97 99 88 99 94 99 94 99 96 99 82 99 91 94 96 99 92 99 94

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

6 10 10 16 7 16 8 11 7 10 12 27 9 18 8 11 7 10 9 17 8 11

50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0

/ 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10 / 10

WARRANTY INFORMATION GE Lighting warrants to the purchaser that each ballast will be free from defects in material or workmanship for period as defined in the attached documents from the date of manufacture when properly installed and under normal conditions of use.

Jul 1, 2010 5:31:15 PM For additional information, visit www.gelighting.com