Delivery program Technical data


Delivery program Technical data - Rackcdn.comhttps://04646a9cf351cc0d3888-b8b406d15fe93f790abb5bf0e9ab7ab3.ssl.cf3.rackcdn.c...

0 downloads 89 Views 344KB Size

Main�switch,�3�pole,�20�A,�Emergency-Stop�function,�90�°,�Lockable�in�the 0�(Off)�position,�rear�mounting

Delivery�program

Part�no.  Article�no.   

T0-2-1/V/SVB 043619

Product range

 

 

Main switch maintenance switch Repair switch

Part group reference

 

 

T0

Stop Function

 

 

Emergency switching off function

 

 

 

With red rotary handle and yellow locking ring

Number of poles

 

 

3 pole

Locking facility

 

 

Lockable in the 0 (Off) position

Degree of Protection

 

 

Front IP65

Design

 

 

rear mounting

 

 

 

Contact sequence

 

 

Switching angle

 

°

Function

 

 

Motor�rating�AC-23A,�50�-�60�Hz

 

 

 

400 V

90

P

kW

5.5

Rated uninterrupted current

Iu

A

20

Number of contact units

 

contact 2 unit(s)

Standards

 

 

IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL Switch-disconnector according to IEC/EN 60947-3

Climatic proofing

 

 

Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature

 

 

 

Open

 

°C

-25 - +50

Enclosed

 

°C

-25 - +40

Overvoltage category/pollution degree

 

 

III/3

Rated impulse withstand voltage

Uimp

V AC

6000

Mechanical shock resistance

 

g

15

Mounting position

 

 

As required

Protection against direct contact when actuated from front (EN 50274)

 

 

Finger and back-of-hand proof

Mechanical variables

 

 

 

Technical�data General

Contacts

Number of poles

 

 

3 pole

Electrical characteristics

 

 

 

12/17/2016

043619 - HPL-ED2016 V27.0 EN

1/6

Rated operational voltage

Ue

V AC

690

Rated uninterrupted current

Iu

A

20

Note on rated uninterrupted current !u

 

 

Rated uninterrupted current Iu is specified for max. cross-section.

Load rating with intermittent operation, class 12

 

 

 

AB 25 % DF

 

x Ie

2

AB 40 % DF

 

x Ie

1.6

AB 60 % DF

 

x Ie

1.3

Short-circuit rating

 

 

 

 

A gG/gL 20

Rated short-time withstand current (1 s current)

Fuse

Icw

Arms

320

Note on rated short-time withstand current lcw

 

 

Current for a time of 1 second

Rated conditional short-circuit current

Iq

kA

6

cos ϕ rated making capacity as per IEC 60947-3

 

A

130

Rated breaking capacity cos ϕ to IEC 60947-3

Switching�capacity

 

A

 

230 V

 

A

100

400/415 V

 

A

110

500 V

 

A

80

690 V

 

A

60

Safe isolation to EN 61140

 

 

 

between the contacts

 

V AC

440

Current heat loss per contact at Ie

 

W

0.6

Current heat loss per auxiliary circuit at Ie (AC-15/230 V)

 

CO

0.6

Lifespan, mechanical

Operations

Maximum operating frequency

Operations/h  

1200

AC

 

 

 

 

 

 

P

kW

 

220 V 230 V

P

kW

3

230 V Star-delta

P

kW

5.5

400 V 415 V

P

kW

5.5

400 V Star-delta

P

kW

7.5

500 V

P

kW

5.5

500 V Star-delta

P

kW

7.5

690 V

P

kW

4

690 V Star-delta

P

kW

5.5

AC-3 Rating, motor load switch

Rated operational current motor load switch

> 0.4

 

 

 

230 V

Ie

A

11.5

230 V star-delta

Ie

A

20

400V 415 V

Ie

A

11.5

400 V star-delta

Ie

A

20

500 V

Ie

A

9

500 V star-delta

Ie

A

15.6

690 V

Ie

A

4.9

690 V star-delta

Ie

A

8.5

 

 

 

 

 

 

Ie

A

20

 

 

 

AC-21A Rated operational current switch 440 V AC-23A Motor rating AC-23A, 50 - 60 Hz

12/17/2016

x 10

6

P

kW

 

230 V

P

kW

3

400 V 415 V

P

kW

5.5

500 V

P

kW

7.5

690 V

P

kW

5.5

043619 - HPL-ED2016 V27.0 EN

2/6

Rated operational current motor load switch

 

 

 

230 V

Ie

A

13.3

400 V 415 V

Ie

A

13.3

500 V

Ie

A

13.3

690 V

Ie

A

7.6

 

 

 

DC DC-1, Load-break switches L/R = 1 ms

 

 

 

Rated operational current

Ie

A

10

Voltage per contact pair in series

 

V

60

Ie

A

 

Rated operational current

Ie

A

1

Contacts

 

Quantity 1

 

 

 

DC-21A

DC-23A, motor load switch L/R = 15 ms 24 V

 

 

 

Rated operational current

Ie

A

10

Contacts

 

Quantity 1

48 V

 

 

 

Rated operational current

Ie

A

10

Contacts

 

Quantity 2

 

 

 

Rated operational current

Ie

A

10

Contacts

 

Quantity 3

 

 

 

Rated operational current

Ie

A

5

Contacts

 

Quantity 3

 

 

 

Rated operational current

Ie

A

5

Contacts

 

Quantity 5

 

 

 

Rated operational current

Ie

A

10

Voltage per contact pair in series

 

V

32

Fault probability

HF

< 10 , < 1 fault in 100000 operations

Solid or stranded

 

mm

Flexible with ferrules to DIN 46228

 

Terminal screw Max. tightening torque

60 V

120 V

240 V

DC-13, Control switches L/R = 50 ms

Control circuit reliability at 24 V DC, 10 mA

Terminal�capacities

-5

2

1 x (1 - 2,5) 2 x (1 - 2,5)

mm

2

1 x (0.75 - 2.5) 2 x (0.75 - 2.5)

 

 

M3.5

 

Nm

1

Notes

 

 

B10d values as per EN ISO 13849-1, table C1

Contacts

 

 

 

Rated operational voltage

Ue

V AC

600

Rated uninterrupted current max.

 

 

 

 

 

 

General use

IU

A

16

Auxiliary contacts

 

 

 

General Use

IU

A

10

Pilot Duty

 

 

A 600 P 600

 

 

 

 

 

 

 

 

 

 

HP

0.5

Technical�safety�parameters: Rating�data�for�approved�types

Main conducting paths

Switching capacity Maximum motor rating Single-phase 120 V AC

12/17/2016

043619 - HPL-ED2016 V27.0 EN

3/6

200 V AC

 

HP

1

240 V AC

 

HP

1.5

Three-phase

 

 

 

200 V AC

 

HP

3

240 V AC

 

HP

3

480 V AC

 

HP

7.5

600 V AC

 

HP

7.5

 

SCCR

 

Basic Rating

 

kA

5

max. Fuse

 

A

50

High fault rating

 

kA

10

max. Fuse

 

A

20, Class J

Terminal capacity

 

 

 

Solid or flexible conductor with ferrule

 

AWG

18 - 14

Terminal screw

 

 

M3.5

Tightening torque

 

lb-in

8.8

 

 

 

Rated operational current for specified heat dissipation

In

A

20

Heat dissipation per pole, current-dependent

Pvid

W

0.6

Equipment heat dissipation, current-dependent

Pvid

W

0

Static heat dissipation, non-current-dependent

Pvs

W

0

Heat dissipation capacity

Pdiss

W

0

Operating ambient temperature min.

 

°C

-25

Operating ambient temperature max.

 

°C

50

 

 

 

10.2 Strength of materials and parts

 

 

 

10.2.2 Corrosion resistance

 

 

Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures

 

 

Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

 

 

Meets the product standard's requirements.

10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects

 

 

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

 

 

Please enquire

10.2.5 Lifting

 

 

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

 

 

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

 

 

Meets the product standard's requirements.

10.3 Degree of protection of ASSEMBLIES

 

 

Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances

 

 

Meets the product standard's requirements.

10.5 Protection against electric shock

 

 

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

 

 

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

 

 

Is the panel builder's responsibility.

10.8 Connections for external conductors

 

 

Is the panel builder's responsibility.

10.9 Insulation properties

Short Circuit Current Rating

Design�verification�as�per�IEC/EN�61439 Technical data for design verification

IEC/EN 61439 design verification

 

 

 

10.9.2 Power-frequency electric strength

 

 

Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage

 

 

Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material

 

 

Is the panel builder's responsibility.

10.10 Temperature rise

 

 

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

 

 

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.12 Electromagnetic compatibility

 

 

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.13 Mechanical function

 

 

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical�data�ETIM�6.0 12/17/2016

043619 - HPL-ED2016 V27.0 EN

4/6

Low-voltage industrial components (EG000017) / Switch disconnector (EC000216) Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Switch disconnector ([email protected] [AKF060010]) Version as main switch

 

 

Yes

Version as maintenance-/service switch

 

 

Yes

Version as safety switch

 

 

No

Version as emergency stop installation

 

 

Yes

Version as reversing switch

 

 

No

Max. rated operation voltage Ue AC

 

V

690

Rated operating voltage

 

V

690 - 690

Rated permanent current Iu

 

A

20

Rated permanent current at AC-21, 400 V

 

A

20

Rated operation power at AC-3, 400 V

 

kW

5.5

Rated short-time withstand current lcw

 

kA

0.32

Rated operation power at AC-23, 400 V

 

kW

5.5

Switching power at 400 V

 

kW

5.5

Conditioned rated short-circuit current Iq

 

kA

6

Number of poles

 

 

3

Number of auxiliary contacts as normally closed contact

 

 

0

Number of auxiliary contacts as normally open contact

 

 

0

Number of auxiliary contacts as change-over contact

 

 

0

Motor drive optional

 

 

No

Motor drive integrated

 

 

No

Voltage release optional

 

 

No

Device construction

 

 

Built-in device fixed built-in technique

Suitable for ground mounting

 

 

Yes

Suitable for front mounting 4-hole

 

 

No

Suitable for front mounting center

 

 

No

Suitable for distribution board installation

 

 

No

Suitable for intermediate mounting

 

 

Yes

Colour control element

 

 

Red

Type of control element

 

 

Door coupling rotary drive

Interlockable

 

 

Yes

Type of electrical connection of main circuit

 

 

Screw connection

Degree of protection (IP), front side

 

 

IP65

Product Standards

 

 

UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94; IEC/EN 60947-3; CE marking

UL File No.

 

 

E36332

UL Category Control No.

 

 

NLRV

CSA File No.

 

 

12528

CSA Class No.

 

 

3211-05

North America Certification

 

 

UL listed, CSA certified

Specially designed for North America

 

 

Yes, with an alternative front plate and/or terminal markings to those of the IEC type in combination with "+NA" (105864)

Suitable for

 

 

Branch circuits, suitable as motor disconnect

Degree of Protection

 

 

IEC: IP65; UL/CSA Type 1, 12

12/17/2016

043619 - HPL-ED2016 V27.0 EN

Approvals

5/6

Dimensions

Shaft and interlock extension with ZAV-T0 + ZVV-T0 possible, max. 4 x 25 = 100 mm ZFS-... Label mount not included as standard Drilling dimensions base Drilling dimensions door

3 padlocks

Additional�product�information�(links) IL03801021Z�(AWA1150-0587)�Cam�switch:�Rear�mounting

IL03801021Z (AWA1150-0587) Cam switch: Rear ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03801021Z2016_07.pdf mounting Form for ordering non-standard front plates

http://ecat.moeller.net/flip-cat/?edition=HPLEN&startpage=4.87

Display flip catalog page.

http://ecat.moeller.net/flip-cat/?edition=K115A&startpage=40

Technical overview cam switch, switchdisconnector

http://de.ecat.moeller.net/flip-cat/?edition=HPLTEv1&startpage=4.2

System overview cam switch T

http://de.ecat.moeller.net/flip-cat/?edition=HPLTEv1&startpage=4.4

System overview switch-disconnector P

http://de.ecat.moeller.net/flip-cat/?edition=HPLTEv1&startpage=4.6

Key to part numbers Cam switch

http://de.ecat.moeller.net/flip-cat/?edition=HPLTEv1&startpage=4.8

Key to part numbers Switch-disconnector

http://de.ecat.moeller.net/flip-cat/?edition=HPLTEv1&startpage=4.8

Switches for ATEX

http://www.coopercrouse-hinds.eu/en/products/25-ex-safety-and-main-current-switches.html

12/17/2016

Eaton Industries GmbH http://www.eaton.eu © 11/2016 by Eaton Industries GmbH 043619 - HPL-ED2016 V27.0 EN

6/6