30RA010-055 Ground-Fault Interrupter Convenience Outlet Accessory

Installation Instructions Part No. 30RA-900---022, 30RA-900---023 SAFETY CONSIDERATIONS

INSTALLATION

Installation of this accessory can be hazardous due to electrical components and equipment location (such as a roof or elevated structure). Only trained, qualified installers and service mechanics should install and service this equipment. When installing this accessory, observe precautions in the literature, labels attached to the equipment, and other safety precautions that apply. • Follow all safety codes. • Wear safety glasses and work gloves. • Use care when handling and installing this accessory. ELECTRIC SHOCK HAZARD To avoid possible electric shock and personal injury, all power to the unit must be disconnected before working on the unit. Tag all disconnects to alert others that the unit is being worked on.

INTRODUCTION The Ground-Fault Circuit Interrupter Convenience Outlet (GFI-CO) accessory provides two auxiliary 115 v, 60 Hz outlets for portable computers, lights, small hand tools and other devices. The current output is limited to 4 amps. See Table 1 for specific package applications. Check each item for shipping damage. If any damage is found, file a claim with the shipping agent immediately. If any item is missing or if any part does not assemble properly, notify your Carrier representative. Table 2 lists the contents of the accessory kits. Table 1 — Accessory Package Usage 30RA UNIT 010-055 (208/230, 230, 460 V) 010-055 (575 V)

Before beginning installation of this equipment, be sure all power to the unit is disconnected, and that tags are properly placed to alert others.

Sizes 30RA010-030 1. Open and tag all electrical disconnects. 2. Open the unit control box door. 3. Locate the bag of mounting hardware and fuses supplied with the accessory. 4. Remove the cover plate in the Scrolling Marquee display bracket (see Fig. 1) and install the GFI-CO receptacle in the opening using the screws provided with the receptacle. 5. Using the no. 8 screws provided, mount the transformer assembly to the fan upright as shown in Fig. 2. Verify that the black and red leads (numbered 1) from the conduit are connected to the transformer primary fuses at the bottom left of enclosure. Verify correct primary connections are made: VOLTAGE

575 V 460 V 230 V 208 V

PRIMARY CONNECTIONS

H1, H2 (Standard 023 package wiring) H1, H4 H2, H4 (Standard 022 package wiring) H3, H4

Operation at 460 v or 208 v WILL require a wiring change.

PACKAGE REQUIRED 30RA-900---022 30RA-900---023

Table 2 — Package Contents ACCESSORY PART NO.

DESCRIPTION

Transformer Assembly, 30RA401664 GFI-CO Receptacle, HY01GF001 Ground wire, 99MD0265XC203018 (30 in.) Power connector, 3RV19155A 30RA-900---022 Screws, no. 81/2-in. long Primary fuse, FNQ-R-21/2 Primary fuse, FNQ-R-31/2 Secondary fuse, FNM-6 Transformer Assembly, 30RA401661 GFI-CO Receptacle, HY01GF001 Ground wire, 99MD0265XC203018 (30 in.) 30RA-900---023 Power connector, 3RV19155A Screws, no. 81/2-in. long Primary fuse, FNQ-R-21/2 Secondary fuse, FNM-6

QTY 1 1 1 1 8 2 2 1 1 1 1 1 8 2 1

GFI-CO

Fig. 1 — Scrolling Marquee Display with Bracket

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 903 Catalog No. 533-00046 Printed in U.S.A. Form 30RA-13SI Pg 1 9-02 Replaces: 30RA-10SI Book 2 Tab 5c

Fig. 2 — Transformer Location and Wiring

11. Attach the black wire labeled no. 1 to the L1 connection. Attach the red wire labeled no. 1 to the L2 connection. Attach the black wire labeled no. 2 to either brass screw on the GFI outlet. Attach the white wire labeled no. 2 to either silver screw on the GFI outlet. (See Fig. 3 for GFI-CO wiring.) 12. Attach one end of the 30-in. long ground wire to the green ground screw on the GFI outlet. Secure the other end of the ground wire from the conduit to the TRAN1 ground terminal. 13. Ensure that all electrical connections are tight and restore power to the unit. 14. Test the GFI-CO by pressing its “Test” button and checking for power at the outlet. If the accessory is incorrectly wired, the GFI-CO may not trip and power may be present at the outlet. If power is present, disconnect all power to the unit, correct the accessory wiring, reconnect the unit power and retest the outlet. 15. When the GFI-CO trips and no power is present at the outlet, restore the circuit by pressing the “Reset” button on the GFI-CO. 16. Remove tags from disconnects and close the control box door. NOTE: After the GFI-CO is installed, periodically test the ground fault feature as described in preceding Steps 14 and 15.

6. Primary and secondary fuses are supplied with each package. A single secondary fuse (FNM-6) should be installed. Install the primary fuses as shown below according to the main power supply of the chiller in the fuse holder clips: Use fuses FNQ-R-21/2 for 460 V and 575 V units Use fuses FNQ-R-31/2 for 208/230 V and 230 V units NOTE: Rejection type fuses are installed one way only. Make sure they are secure in the fuse holder clips. 7. Using the screws provided, install the cover on the transformer box. 8. Route the other end of the conduit away from fan and refrigerant piping to back of control box. Remove knockout in control box below Main Base Board (MBB) and above row of condenser fan, heater and pump contactors. 9. Attach conduit to back of control box. 10. Install power connector from kit (3RV19155A) on top of a condenser fan or pump manual starter that has only 1 bus bar connection. Do NOT install or disturb the wiring to the cooler/pump heater circuit breaker (MS-CHC-L3) connection. If the MS-CHC circuit breaker is the only available point of connection, crimp the no. 8 spade terminals provided on the no. 1 labeled black and red wires.

Sizes 30RA032-055 (FROM TRAN 2 SEC L1) BLK

LINE

SILVER SCREW (FROM TRAN 2 SEC L2) WHT

1. Open and tag all electrical disconnects. 2. Open the unit center control box door (see Fig. 4). Open the left control box door and remove the inner cover. 3. Locate the bag of mounting hardware and fuses supplied with the accessory. 4. Remove the cover plate in the Scrolling Marquee display bracket and install the GFI-CO receptacle in the opening using the screws provided with the receptacle. 5. The sheet metal box and cover supplied with the transformer assembly are NOT used for these models. Remove the transformer from the sheet metal box. Using the no. 8 screws provided, mount the transformer to the sheet metal pan in the far right side of the control panel. Remove the fuse block from the sheet metal box and mount near the transformer. See Fig. 5.

BRASS SCREW

LOAD

GRN-YEL

GROUND AT TRAN 1 LOCATION

Fig. 3 — GFI Receptacle Wiring (Option)

2

GFI-CO TO NEC FUSED DISCONNECT

Fig. 4 — Component Arrangement Using field-supplied wire, connect the transformer secondary X2 terminal to the TRAN1 ground terminal location. 7. Primary and secondary fuses are supplied with each package. A single secondary fuse (FNM-6) should be installed. Install the primary fuses as shown below according to the main power supply of the chiller in the fuse holder clips: Use fuses FNQ-R-21/2 for 460 V and 575 V units Use fuses FNQ-R-31/2 for 208/230 V and 230 V units NOTE: Rejection type fuses are installed one way only. Make sure they are secure in the fuse holder clips. 8. Install power connector from kit (3RV19155A) on top of condenser fan starter MS-FC-HS (sizes 032-040) or MS-FC-B2 (sizes 042-055). 9. Attach the black wire labeled no. 1 to the L1 connection. Attach the red wire labeled no. 1 to the L2 connection. 10. Attach the black wire labeled no. 2 to either brass screw on the GFI outlet. Attach the white wire labeled no. 2 to either silver screw on the GFI outlet. See Fig. 3 for GFI-CO wiring. 11. Attach one end of the 30-in. long ground wire to the green ground screw on the GFI outlet. Secure the other end of the ground wire to the TRAN1 ground terminal. 12. Ensure that all electrical connections are tight and restore power to the unit. 13. Test the GFI-CO by pressing its “Test” button and checking for power at the outlet. If the accessory is incorrectly wired, the GFI-CO may not trip and power may be present at the outlet. If power is present, disconnect all power to the unit, correct the accessory wiring, reconnect the unit power and retest the outlet. 14. When the GFI-CO trips and no power is present at the outlet, restore the circuit by pressing the “Reset” button on the GFI-CO. 15. Remove tags from disconnects and close the control box door. NOTE: After the GFI-CO is installed, periodically test the ground fault feature as described in preceding Steps 13 and 14.

TRAN 2

Fig. 5 — Control Panel Detail 6. Remove all 5 wires from the conduit assembly supplied with the accessory. Discard the conduit. Make the following connections: PRIMARY VOLTAGE 575 V 460 V 230 V 208 V

PRIMARY CONNECTIONS Black #1 to Fuse, Fuse to H1 Red #1 to Fuse, Fuse to H2 Black #1 to Fuse, Fuse to H1 Red #1 to Fuse, Fuse to H4 Black #1 to Fuse, Fuse to H2 Red #1 to Fuse, Fuse to H4 Black #1 to Fuse, Fuse to H3 Red #1 to Fuse, Fuse to H4

SECONDARY CONNECTIONS Black #1 to Fuse White #2 to X2 Black #1 to Fuse White #2 to X2 Black #1 to Fuse White #2 to X2 Black #1 to Fuse White #2 to X2

3

Copyright 2002 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. PC 903 Catalog No. 533-00046 Printed in U.S.A. Form 30RA-13SI Pg 4 9-02 Replaces: 30RA-10SI Book 2 Tab 5c