LED Power Supply


[PDF]LED Power Supply - Rackcdn.comhttps://c761eecbd79071d9c578-5541377ae4e44cfbbc0efe790ed7f783.ssl.cf1.rackcdn...

6 downloads 500 Views 388KB Size

GE Lighting

LED Power Supply Outdoor Dimming Driver GE150/1050/MV-GL 12161

imagination at work

Outdoor Dimming Driver GE150/1050/MV-GL Description: 150W 0.53/0.7/1.05A Dimmable Class 1 PSU Input Voltage: 120-277V Input Frequency: 50-60Hz ROHS Compliant: Yes Max Output Power (W)

150

Output Current (A)

Output Voltage (V)

0.525 ± 5%

Efficiency @ Full Load 120V

230V

277V

140-280

>91%

>92%

>93%

0.700 ± 5%

105-210

>90%

>92%

1.05 ± 5%

70-140

>89%

>91%

Max Input Current (A)

1.60 @ 120V >92% 0.80 @ 277V >91%

20%

Min PF @75W Output

0.9

Max Inrush Current (A/mS)

Protocol Source

See

0-10V

Page 4

Output + (Red)

Line (Black) TVSS Ground (Yellow)

Max THD @75W Output

GE-XXXXX LED Driver

Neutral (White)

Output -1A (Blue) Output -0.7A (Yellow) Output -0.53A (Orange) Dim + (Violet) Dim - (Grey)

Isolated Dimming

Weight (lbs/kg)

IP Rating

0.5mA 100% - 10%

2.2/1

IP66

0-10V

0.5mA 100% - 10%

2.2/1

IP66

0-10V

0.5mA 100% - 10%

2.2/1

IP66

Length in. (cm) Color 12 (30.5) Black (L) 12 (30.5) Yellow (TVSS-GND) 12 (30.5) White (N) 12 (30.5) Violet (+Dim) 12 (30.5) Grey (-Dim) 12 (30.5) Red (+ Output) 12 (30.5) Blue (-1A Output) 12 (30.5) Yellow (-700mA Output) 12 (30.5) Orange (-530mA Output)

Product Features Physical • Unit must be installed within an electrical enclosure. • Enclosure wiring must be rated to 600V & 105°C or higher.

Performance • • • • • • • • • •

Classified as Class 1 as per UL8750. Dimming circuit is classified as Class 2 as stipulated in UL1310. Minimum ambient operating temperature: -40°C. Maximum allowable case temperature: 80°C. For reliability and failure rate information, contact GE Technical Sales Representative. Output current reduces if the case temperature exceeds 85°C. UL listed for operation in dry/damp locations (IP66). Tolerates of extended open circuit and short circuit conditions. Compliant to FCC Title 47 Part 15 Class A Surge resistance per IEEE/ANSI C136.2-2015 Location C-Low (6kV/3kA) • Ground Leakage current of <= 0.4 mA

UL Conditions of Acceptability – E340135 • • • •

The unit has been examined to comply with Class 1 Output Criteria The unit is only to be used in dry or damp locations The metal casing must be connected to EARTH. TVSS-GND (Yellow wire) shall be connected to fixture ground after hi-pot test using closest tab screw. THIS IS NOT A SAFETY GROUND!

Current Dimming Range Range (%)

Technical Information GE150/1050/MV-GL

Lifetime (kHrs) vs Case Temperature (°C 120

Lifetime (KHrs)

100

80

60

40

20

0 35

25

45

55

65

75

85

Driver Case Temperature (°C)

Iout / Iout N (%)

Output current vs Dim Voltage 110 100 90 80 70 60 50 40 30 20 10 0

0.530 A 0.700 A 1.05 A 012345678

91

01

11

2

Vdim (V)

Efficiency vs Output Voltage @ 120V 60Hz 94 Efficiency [%]

92 90 88 86

1050mA

84

700mA 525mA

82 80 0

25

50

75

100

125

150

175

200

225

250

275

300

Output Voltage (V)

Efficiency vs Output Voltage @ 277V 60Hz 94 Efficiency [%]

92 90 88 86

1050mA

84

700mA 525mA

82 80 0

25

50

75

100

125

150

175

Output Voltage (V)

200

225

250

275

300

Technical Information GE150/1050/MV-GL

PF vs Output Voltage @ 120V 60Hz Power Factor

1.000 0.995 0.990

1050mA 700mA

0.985

525mA

0.980 0

25

50

75

100

125

150

175

200

225

250

275

300

Output Voltage

Power Factor

PF vs Output Voltage @ 277V 60Hz 1.00 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90

1050mA 700mA 525mA

0

25

50

75

100

125

150

175

200

225

250

275

300

Output Voltage

THD vs Output Voltage @ 120V 60Hz 6

THD %

5 4 3

1050mA

2

700mA

1

525mA

0 0

25

50

75

100

125

150

175

200

225

250

275

300

Output Voltage

THD %

THD vs Output Voltage @ 277V 60Hz 20 18 16 14 12 10 8 6 4 2 0

1050mA 700mA 525mA

0

25

50

75

100

125

150

175

200

225

250

275

300

Output Voltage

Input Inrush Current

Input Ground Leakage Current

Input Voltage [Vrms]

Peak Current Pulse [Apk]

Pulse Duration (50% of Peak) [ms]

Input Voltage [Vrms]

Leakage Current [mA]

120

31

0.1

S1 ON

S1 Off

120

0.18

208

0.18

277

60

0.1

Product Dimensions GE150/1050/MV-GL

MULTIPLE OUTPUT -RED, BLUE, ORANGE, YELLOW LEADS 0.9 [.0]

DIMMING VIOLET, GREY LEADS

10.2 [.4]

38.20 [1.5] 295.5 [11.6]

7.2 [.3]

8.4 [.3]

INPUT BLACK, WHITE LEADS YELLOW TVSS-GND

240.5 [9.5] 211.1 [8.3] 226.2 [8.9] 42.9 59.1 60.7 [1.7] [2.3] [2.4]

4 X R3 [.1]

8.1 [.3]

2 [.1]

207.6 MAX PCB LENGTH [8.2]

6 [.2]

3 [.1] 1 [.0]

55.5 MAX PCB WIDTH [2.2]

1. PUNCH HOLE MIN BEND RADIUS 0.8 MM 2. PART NOMINAL PER 3D DATABASE SUPPLIED AT SAME REVISION AS THIS DRAWING, ONLY CRITICAL DIMENSIONS ARE SHOWN. 3. PART MUST BE FREE OF SHARP EDGES OR BURRS.

PUNCH HOLE

DETAIL A SCALE 4:1

Product Label

(L) BLACK

AVERTISSEMENT !

(TVSS-FGND) YELLOW

RISK OF ELECTRIC SHOC K

Turn power off before servicing. Properly ground power supply and fixture

RISQUE DE CHOC ÉLECTRIQUE IMPORTANT: After HiPot test connect TVSSFGND to fixture using the closest tab screw.

(N) WHITE

VOUT: 70-280V IOUT: 0.53A RED/ORG IOUT: 0.7A RED/YEL IOUT: 1.05A RED/BLU POUT: 150W

Suitable for dry and damp locations tc = 80°C max VDIM: 0-10V

CASE MUST BE GROUNDED

E34013 5

www.gelighting.com GE and the GE Monogram are trademarks of the General Electric Company. All other trademarks are the property of their respective owners. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions. GE Lighting and GE Lighting Solutions, LLC are businesses of the General Electric Company. © 2015 GE. OLP3063 (Rev 09/30/15)

OUTPUT

(+OUT) RED (-OUT_0.53A) ORANGE (-OUT_0.7A) YELLOW (-OUT_1.05A) BLUE (+DIM) VIOLET (-DIM) GRAY

Tc

DIMMING

INPUT

G E150/1050/MV-GL

WARNING /

Déconnectez l’alimentation électeique avant d’installer ce produit .

Measure 20mm down side

LED POWER SUPPLY

VIN nom: 120-230-277V~ Freq: 50/60Hz Iin max: 1.6A~ PF min: 0.9

S/N: sssss yy ddd PWS009 0 Made in China