PS1400 MVOLT INSTALLATION INSTRUCTIONS ! IMPORTANT SAFEGUARDS ! WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. To prevent high voltage from being present on red & yellow output leads prior to installation, inverter connector must be open. Do not join inverter connector until installation is complete and AC power is supplied to the emergency ballast. 2. This product is for use with one 17 W through 215 W (2' - 8') or two 17 W through 40 W (2' - 4') single pin or bipin fluorescent lamps, including standard, energy saving, HO, VHO, circline, U-shaped and rapid-start (4-pin) Long compact fluorescent lamps. 3. Make sure all connections are in accordance with the National Electrical Code and any local regulations. 4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing. 5. This emergency ballast is for factory or field installation in either the ballast channel or on top of the fixture. 6. This product is suitable for use in damp locations where the ambient temperature is 0ºC minimum, +50ºC maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is not suitable for heated air outlets and wet or hazardous locations. 7. An unswitched AC power source is required (120 through 277 VAC, 50/60 Hz). 8. Do not install near gas or electric heaters. 9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable. Contact the manufacturer for information on service. 10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 11. Do not use this product for other than intended use. 12. Servicing should be performed by qualified service personnel.
SAVE THESE INSTRUCTIONS CONTAINS NICKEL-CADMIUM RECHARGEABLE BATTERY. MUST BE RECYCLED OR DISPOSED OF PROPERLY. Ni - Cd
05/13/11 POWER SENTRY/ACCUPRO 1400 Lester Road, Conyers, Georgia 30012 • Tech Support 1-888-300-7017 • www.powersentrysafety.com E71446 75000205
INSTALLATION WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED AND YELLOW OUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO NOT JOIN INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY BALLAST. NOTE: Make sure the necessary branch circuit wiring is available. An unswitched source of power is required. The emergency ballast must be fed from the same branch circuit as the AC ballast. 1. Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency ballast either in the ballast channel (see Illustrations 1&2) or on top of the fixture* (see Illustration 3). 2. Select the appropriate wiring diagram to connect the emergency ballast to the AC ballast and lamp. Make sure all connections are in accordance with the National Electrical Code and any local regulations.
ILLUSTRATION 3
ILLUSTRATION 2
ILLUSTRATION 1
*For installation on top of the fixture, wire bundle covers may be required by state or local codes. These covers are available from the manufacturer as an accessory kit and must be ordered separately. Call your local distributor or the factory for complete infomation.
3. Install the test switch through the ballast channel cover of a troffer or through the side of a strip fixture. Drill a 1/2" hole and install the switch as shown (see Illustration 1&2). Wire the test switch so that it removes AC power from both the emergency ballast and the AC ballast at the same time (see Illustration 4). 4. Refer to Illustration 5 and install the charging indicator light so that it will be visible after the fixture is installed. NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. If a detached charging indicator light is used, connect by matching wire colors and install as shown in Illustration 5. 5. In a readily visible location, attach the label “CAUTION–This Unit Has More Than One Power Connection Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency Power Supplies Before Servicing.”
ILLUSTRATION 4 DOUBLE POLE OPTION SWITCHED FIXTURE
UNSWITCHED FIXTURE TEST SWITCH
TEST SWITCH
HOT
BLK
BLK
WALL SWITCH
BLACK
WHITE
WHT/BLK WHT/RED RED
COM
RED
BLACK
HOT
AC BALLAST
BLK
BLK
BLACK
WHITE
WHT/BLK WHT/RED
EMERGENCY BALLAST
WHITE
RED
COM
2
RED
BLACK
WHITE
AC BALLAST
EMERGENCY BALLAST
ILLUSTRATION 5 TROFFER STYLE FIXTURE
STRIP STYLE FIXTURE Fixture
Fixture Charging Indicator Light
Charging Indicator Light Violet (+)
Violet (+)
Brown (–)
Brown (–)
5/8" Black Bushing
1/2" White Bushing
1/2" White Bushing
5/8" Black Bushing
1/2" Punch
NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. 6. After installation is complete, supply AC power to the emergency ballast and join the inverter connector. 7. A short-term discharge test may be conducted after the emergency ballast has been charging for one hour. Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION.
OPERATION During normal operation AC power is applied, the charging indicator light is illuminated, indicating that the battery is being charged. When power fails, the emergency ballast automatically switches to emergency power (internal battery), operating either one or two lamps for a minimum of 90 minutes. When AC power is restored, the emergency ballast returns to the charging mode and delays AC ballast operation for approximately three seconds to prevent false-tripping of AC ballast (end-of-lamp-life) shutdown circuits.
MAINTENANCE Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically to ensure that it is working. The following schedule is recommended: 1. Visually inspect the charging indicator light monthly. It should be illuminated. 2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. Either one or two lamps should operate at reduced illumination. 3. Conduct a 90-minute discharge test once a year. Either one or two lamps should operate at reduced illumination for at least 90 minutes.
REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL.
WIRING DIAGRAMS The following diagrams are typical schematics only. May be used with other ballasts. Consult the factory for other wiring diagrams. Emergency Ballast and AC Ballast must be fed from the SAME BRANCH CIRCUIT.
Table 1 LAMP
BASE TYPE
T8,T9,T10,T12 (1”, 1¼”, 1½”)
Single or Bipin
LONG COMPACT
4-PIN (2G11)
(DIAMETER)
WATTAGE (Length)
17 - 40 W (2'-4') 40 - 215 W (5' -8') 18 - 39 W 40 - 55 W
3
NO. of LAMPS (EMERGENCYMODE)
BROWN CONNECTOR
1
CLOSED
2
OPEN
1
OPEN
1
CLOSED
2
OPEN
1
CLOSED
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT. TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
WIRING DIAGRAMS for 1-LAMP emergency operation FIG A
ONE (1) LAMP RAPID START BALLAST
FIG B
ONE (1) LAMP INSTANT START BALLAST
WALL SWITCH
HOT
WALL SWITCH
WHT/RED B L K
TEST SWITCH B L K
INVERTER CONNECTOR CHARGING INDICATOR
COMMON
RED WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
E M E R G E N C Y
B A L L A S T
BROWN BROWN RED
HOT
WARNING: Refer to Table 1 before connecting
YELLOW YEL/BLK BLU/WHT BLUE
LAMP
BLUE BLUE
WHT/RED B L K
INVERTER CONNECTOR
TEST SWITCH
CHARGING INDICATOR
B L K
RED RED
1 LAMP RAPID START BALLAST
COMMON
RED WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
E M E R G E N C Y
B A L L A S T
BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE
FIG D
TWO (2) LAMP RAPID START BALLAST WALL SWITCH
HOT
TEST SWITCH B L K
INVERTER CONNECTOR CHARGING INDICATOR
COMMON
TWO (2) LAMP INSTANT START BALLAST
RED WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
E M E R G E N C Y
BROWN BROWN
B A L L A S T
HOT
WARNING: Refer to Table 1 before connecting
WHT/RED B L K
RED YELLOW YEL/BLK
LAMP 1 (EMERGENCY)
BLU/WHT
BLUE
BLUE
BLUE
2 LAMP RAPID START BALLAST
RED RED
INVERTER CONNECTOR
TEST SWITCH
CHARGING INDICATOR
B L K
LAMP 2
COMMON
YELLOW YELLOW
RED WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
E M E R G E N C Y
B A L L A S T
BROWN BROWN RED
FIG F
THREE (3) LAMP RAPID START BALLAST
TEST SWITCH B L K
INVERTER CONNECTOR CHARGING INDICATOR
COMMON
RED WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
E M E R G E N C Y
B A L L A S T
WARNING: Refer to Table 1 before connecting
YELLOW YEL/BLK BLU/WHT BLUE
BLU/WHT YELLOW YELLOW
3 LAMP RAPID START BALLAST
TEST SWITCH B L K
INVERTER CONNECTOR CHARGING INDICATOR
COMMON
LAMP 2
BLU/WHT
COMMON
LAMP 3
RED WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
E M E R G E N C Y
B A L L A S T
TEST SWITCH B L K
CHARGING INDICATOR
COMMON
LAMP 2
RED
BROWN (-)
WHITE WHT/BLK
B A L L A S T
BROWN BROWN RED
WARNING: Refer to Table 1 before connecting
YELLOW YEL/BLK BLU/WHT
LAMP 1(EMERGENCY)
BLUE
BLUE
FIG H
BLUE
3 LAMP INSTANT START BALLAST
BLUE
LAMP 2
LAMP 3
RED
FOUR (4) LAMP INSTANT START BALLAST
HOT
BROWN BROWN RED
WARNING: Refer to Table 1 before connecting
YELLOW YEL/BLK
LAMP 1 (EMERGENCY)
BLU/WHT
RED
YELLOW
BLUE
RED
YELLOW
4 LAMP RAPID START BALLAST
BLU/WHT BLU/WHT
WHT/RED B L K
TEST SWITCH B L K
INVERTER CONNECTOR CHARGING INDICATOR
RED WHITE VIOLET (+) BROWN (-)
LAMP 2 COMMON
LAMP 3
WHITE WHT/BLK
E M E R G E N C Y
B A L L A S T
BROWN BROWN RED
BLUE
BRN BRN BLUE BLUE
WARNING: Refer to Table 1 before connecting
YELLOW YEL/BLK BLU/WHT
LAMP 1 (EMERGENCY)
YELLOW BLUE
BLACK WHITE
BLUE
4 LAMP INSTANT START BALLAST
RED
LAMP 3
YELLOW RED
LAMP 4
FIG J
LAMP 2
LAMP 4
TWO (2) LAMP COMPACT RAPID START BALLAST WALL SWITCH
WHT/RED INVERTER CONNECTOR
VIOLET (+)
E M E R G E N C Y
BLACK WHITE
ONE (1) LAMP COMPACT RAPID START BALLAST B L K
RED WHITE
RED RED
WALL SWITCH
HOT
2 LAMP INSTANT START BALLAST
WALL SWITCH
BLACK WHITE
FIG I
CHARGING INDICATOR
B L K
FOUR (4) LAMP RAPID START BALLAST WHT/RED
B L K
INVERTER CONNECTOR
TEST SWITCH
LAMP 1 (EMERGENCY) BLUE BLUE
WHT/RED B L K
WALL SWITCH
HOT
BLUE
THREE (3) LAMP INSTANT START BALLAST
HOT
BROWN BROWN RED
BLACK WHITE
FIG G
BLUE
WALL SWITCH
WHT/RED B L K
LAMP 1(EMERGENCY)
BLUE
BLACK WHITE
WALL SWITCH
HOT
WARNING: Refer to Table 1 before connecting
YELLOW YEL/BLK BLU/WHT
BLACK WHITE
FIG E
1 LAMP INSTANT START BALLAST
WALL SWITCH
WHT/RED B L K
LAMP RED
BLUE
BLACK WHITE
BLACK WHITE
FIG C
WARNING: Refer to Table 1 before connecting
RED WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
E M E R G E N C Y
B A L L A S T
BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE
B L K
LAMP BLUE BLUE
BLACK
WHT/RED
HOT
WARNING: Refer to Table 1 before connecting
TEST SWITCH
RED RED
B L K
1 LAMP RAPID START BALLAST
INVERTER CONNECTOR CHARGING INDICATOR
COMMON
RED WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
E M E R G E N C Y
B A L L A S T
BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE
WARNING: Refer to Table 1 before connecting
LAMP 1 BLUE BLUE
BLACK WHITE
WHITE
4
2 LAMP RAPID START BALLAST
YELLOW
(EMERGENCY)
YELLOW RED RED
LAMP 2
WIRING DIAGRAMS for 2-LAMP emergency operation (2´- 4´, 17- 40 W lamps only) FIG K
FIG L
TWO (2) LAMP RAPID START BALLAST
TWO (2) LAMP INSTANT START BALLAST WALL SWITCH
HOT
WALL SWITCH
HOT
WHT/RED B L K
TEST SWITCH B L K
INVERTER CONNECTOR CHARGING INDICATOR
COMMON
RED
E M E R G E N C Y
WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
B A L L A S T
BROWN BROWN YELLOW YEL/BLK RED
LAMP 1
BLUE BLUE
BLU/WHT BLUE
RED RED
2 LAMP RAPID START BALLAST
WHT/RED B L K
WARNING: Do NOT connect brown connector TEST SWITCH
B L K
LAMP 2
RED
INVERTER CONNECTOR
WHITE VIOLET (+)
CHARGING INDICATOR
BROWN (-)
WHITE WHT/BLK
COMMON YELLOW YELLOW
E M E R G E N C Y
B A L L A S T
BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE
THREE (3) LAMP RAPID START BALLAST
FIG N
WALL SWITCH
WHT/RED B L K
TEST SWITCH B L K
INVERTER CONNECTOR CHARGING INDICATOR
COMMON
RED
E M E R G E N C Y
WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
B A L L A S T
HOT
BROWN BROWN RED
WARNING: Do NOT connect brown connector
YELLOW YEL/BLK BLUE BLUE
BLU/WHT BLUE
TEST SWITCH
BLU/WHT BLU/WHT
3 LAMP RAPID START BALLAST
YELLOW YELLOW
B L K
B L K
RED
INVERTER CONNECTOR CHARGING INDICATOR
COMMON
BROWN (-)
WHITE WHT/BLK
LAMP 3
B A L L A S T
WARNING: Do NOT connect brown connector
YELLOW RED
LAMP 1 (EMERGENCY)
YEL/BLK BLU/WHT BLUE
BLUE BLUE
BLACK WHITE
RED RED
E M E R G E N C Y
WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
B A L L A S T
BROWN BROWN RED
FIG P
3 LAMP INSTANT START BALLAST
BLUE
LAMP 2 (EMERGENCY)
LAMP 3
RED
FOUR (4) LAMP INSTANT START BALLAST HOT
WARNING: Do NOT connect brown connector
WHT/RED B L K
YELLOW YEL/BLK
LAMP 1 (EMERGENCY)
BLU/WHT BLUE
TEST SWITCH
YELLOW YELLOW
RED RED
4 LAMP RAPID START BALLAST
BLU/WHT BLU/WHT
B L K
LAMP 2 (EMERGENCY)
RED
INVERTER CONNECTOR
WHITE VIOLET (+)
CHARGING INDICATOR
BROWN (-)
WHITE WHT/BLK
COMMON
LAMP 3
BRN BRN BLUE BLUE
BLACK WHITE
FIG Q
VIOLET (+)
CHARGING INDICATOR
E M E R G E N C Y
WALL SWITCH
WHT/RED
TEST SWITCH
WHITE
COMMON
WALL SWITCH
B L K
RED
INVERTER CONNECTOR
LAMP 2 (EMERGENCY)
FOUR (4) LAMP RAPID START BALLAST
HOT
BROWN BROWN
WHT/RED B L K
LAMP 1(EMERGENCY)
BLACK WHITE
FIG O
LAMP 2
2 LAMP INSTANT START BALLAST
THREE (3) LAMP INSTANT START BALLAST
WALL SWITCH
HOT
LAMP 1
RED BLUE
BLUE
BLACK WHITE
BLACK WHITE
FIG M
WARNING: Do NOT connect brown connector
E M E R G E N C Y
B A L L A S T
BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE
WARNING: Do NOT connect brown connector
LAMP 1 (EMERGENCY)
YELLOW BLUE
BLACK WHITE
BLUE
4 LAMP INSTANT START BALLAST
RED
LAMP 2 (EMERGENCY)
LAMP 3
YELLOW RED
LAMP 4
LAMP 4
TWO (2) COMPACT LAMP RAPID START BALLAST WALL SWITCH
WHT/RED
HOT B L K TEST SWITCH B L K
INVERTER CONNECTOR CHARGING INDICATOR
COMMON
RED
E M E R G E N C Y
WHITE VIOLET (+) BROWN (-)
WHITE WHT/BLK
B A L L A S T
BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE
WARNING: DO NOT connect brown connector
LAMP 1 BLUE BLUE
BLACK WHITE
YELLOW
2 LAMP RAPID START BALLAST
YELLOW RED RED
LAMP 2
WIRING DIAGRAMS for EMERGENCY-ONLY fixtures FIG R HOT
ONE (1) LAMP WITHOUT AC BALLAST (16W-215W) WHT/RED
(CAP)
B L K TEST SWITCH B L K
RED
INVERTER CONNECTOR
WHITE VIOLET (+)
CHARGING INDICATOR
BROWN (-)
WHITE WHT/BLK
COMMON (CAP)
FIG T B L K
TEST SWITCH B L K
B A L L A S T
BROWN BROWN RED
WARNING: Refer to Table 1 before connecting
YELLOW YEL/BLK BLU/WHT BLUE
LAMP (CAP)
RED WHITE VIOLET (+)
CHARGING INDICATOR
BROWN (-)
COMMON (CAP)
WHITE WHT/BLK
TWO (2) LAMPS WITHOUT AC BALLAST (17W-40W) WHT/RED
(CAP)
B L K TEST SWITCH B L K
INVERTER CONNECTOR
BROWN (-)
WHITE WHT/BLK
(CAP)
E M E R G E N C Y
B A L L A S T
BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE
WARNING: Refer to Table 1 before connecting
FIG U B L K
(CAP) (CAP)
TEST SWITCH B L K
E M E R G E N C Y
BROWN BROWN
B A L L A S T
WARNING: Do NOT connect brown connector
RED YELLOW YEL/BLK BLU/WHT BLUE
LAMP 1 (CAP) (CAP)
LAMP 2
TWO (2) 4-PIN COMPACT LAMPS WITHOUT AC BALLAST (16W-39W) (CAP)
HOT
LAMP
RED WHITE VIOLET (+)
CHARGING INDICATOR
COMMON
WHT/RED
INVERTER CONNECTOR
HOT
(CAP)
ONE (1) 4-PIN COMPACT LAMP WITHOUT AC BALLAST (16W-55W) (CAP)
HOT
E M E R G E N C Y
FIG S
WHT/RED
INVERTER CONNECTOR
RED WHITE VIOLET (+)
CHARGING INDICATOR
BROWN (-)
COMMON (CAP)
WHITE WHT/BLK
E M E R G E N C Y
B A L L A S T
BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE
WARNING: Do NOT connect brown connector LAMP 1 (CAP) (CAP)
LAMP 2