Architectural Testing

ANSI/AAMA/NWWDA 101/I.S. 2-97 TEST REPORT Rendered to: PEACHTREE DOORS & WINDOWS SERIES/MODEL: Symmetry 200 Vinyl Direct Set PRODUCT TYPE: Vinyl Fixed Window

Title

Summary of Results

Rating

F-C50 72x72

Air Infiltration

<0.01 cfm/ft2

Water Resistance Test Pressure

7.50 psf

Uniform Load Deflection Test Pressure

±50.00 psf

Uniform Load Structural Test Pressure

±75.00 psf

Forced Entry Resistance

Grade 10

Reference should be made to ATI Report Identification No. 55828.02-602-44 for complete test specimen description and data.

5906 Saxon Avenue Schofield, WI 54476 phone: 715-241-8624 fax: 715-241-8425 www.archtest.com

Architectural Testing

ANSI/AAMA/NWWDA 101/I.S 2-97 TEST REPORT Rendered to: PEACHTREE DOORS & WINDOWS 1000 Southview Drive Mosinee, Wisconsin 54455 ATI Report Identification No: 55828.02-602-44 Test Date: 02/03/05 Through: 02/28/05 Report Date: 03/01/05 Expiration Date: 02/28/09 Project Summary: Architectural Testing, Inc. (ATI) was contracted by Peachtree Doors & Windows to perform testing on a Series/Model Symmetry 200 Vinyl Direct Set, Vinyl Fixed Window at Architectural Testing, Inc. in Schofield, Wisconsin. The sample tested successfully met the performance requirements for an F-C50 72x72 rating. Test specimen description and results are reported herein. Test Specification(s): The test specimen was evaluated in accordance with the following: AAMA 1701.2-02, Primary Window and Sliding Glass Door Voluntary Standard for Utilization in Manufactured Housing. ANSI/AAMA/NWWDA 101/I.S.2-97, Voluntary Performance Specification for Aluminum, Vinyl (PVC) and Wood Windows and Doors. Uniform load structural testing was also performed per North Carolina Building Code 613.2Mullions. Test Specimen Description: Series/Model: Symmetry 200 Vinyl Direct Set Product Type: Vinyl Fixed Window Overall Size: 5' 11 -1/2" wide by 5' 11 -1/2" high Overall Area: 35.50 ft2 Finish: All vinyl was white.

5906 Saxon Avenue Schofield, WI 54476 phone: 715-241-8624 fax: 715-241-8425 www.archtest.com

Architectural Testing

55828.02-602-44 Page 2 of 5

Test Specimen Description: (Continued) Glazing Details: The frame utilized nominal 3/4" thick insulated glass fabricated from two sheets of 5/32" thick clear tempered glass separated by a 7/16" butyl spacer material with aluminum substrate-dual sealed spacer system. The glass was set from the interior against foam glazing tape and a continuous bed of silicone sealant. A vinyl glazing bead was snap-fit at the exterior on all four sides. Frame Construction: The vinyl frame members were miter cut and employed welded corner construction Installation: The test specimen was installed into a nominal 2x6 wood buck utilizing an applied nailing flange on all four sides. The unit was set into a continuous bed of silicone sealant. The flange was secured to the wood buck with #8 by 1 -5/8" long screws spaced approximately 10" on center. Silicone was applied over the screw heads and the perimeter of the nailing flange. Test Results: The results are tabulated as follows: AAMA 1701.2-02 Paragraph

Title of Test - Test Method

2.2.3.1

Exterior Pressure per ASTM E 330-02 25.00 psf (positive) PASS

No breakage or permanent set impairing operation

2.2.3.2

Interior Pressure per ASTM E 330-02 12.50 psf (negative) PASS

No breakage or permanent set impairing operation

2.2.4

Air Infiltration per ASTM E 283-04 1.57 psf (25 mph) <0.01 cfm/ft2

Results

Allowed

0.50 cfm/ft2

55828.02-602-44 Page 3 of 5

Architectural Testing

Test Results: (Continued) Paragraph

Title of Test - Test Method

2.2.5

Water Resistance per ASTM E 547-00 2.86 psf No leakage

Results

Allowed

No leakage

AAMA/NWWDA 101/I.S.2-97 Paragraph

Title of Test - Test Method

2.1.2

Air Infiltration per ASTM E 283-04 (See Note #1) 1.57 psf (25 mph) <0.01 cfm/ft2 0.3 cfm/ft2 max. 2 6.24 psf (50 mph) <0.01 cfm/ft --

Results

Allowed

Note #1: The tested specimen meets (or exceeds) the performance levels specified in ANSI/AAMA/NWWDA 101/I.S. 2-97 for air infiltration. 2.1.3

Water Resistance per ASTM E 547-00 (See Note #2)

2.1.4.2

Uniform Load Structural per ASTM E 330-02 (See Note #2)

Note #2: The client opted to start at a pressure higher than the minimum required. Those results are listed under “Optional Performance.” 2.1.7

Welded Corner Test

2.1.8

Forced Entry Resistance per ASTM F 588-04 Type: D

Meets as stated

Meets as stated

Grade: 10

Hand and Tool Manipulation Test No entry

No entry

Optional Performance Paragraph

Title of Test - Test Method

4.3

Water Resistance per ASTM E 547-00 and ASTM E 331-00 7.50 psf No leakage No leakage

Results

Allowed

55828.02-602-44 Page 4 of 5

Architectural Testing

Test Results: (Continued) Paragraph

Title of Test - Test Method

4.4.1

Uniform Load Deflection per ASTM E 330-02 (Loads were held for 60 seconds) 50.00 psf (positive) No damage 50.00 psf (negative) No damage

Results

Allowed

See Note #3 See Note #3

Note #3: The Uniform Load Deflection test is not a requirement of ANSI/AAMA/NWWDA 101/I.S. 2-97 for this product designation. The deflection data is recorded in this report for special code compliance and information only. 4.4.2

Uniform Load Structural per ASTM E 330-02 (Loads were held for 10 seconds) 75.00 psf (positive) No damage 75.00 psf (negative) No damage

No damage No damage

Note: A lead check swab test was performed on all polymeric profiles. The test result was negative for the presence of lead (ph). Detailed drawings, representative samples of the test specimen, and a copy of this report will be retained by ATI for a period of four years from the original test date. The above results were secured by using the designated test methods and they indicate compliance with the performance requirements of the above referenced specification. This report does not constitute certification of this product, which may only be granted by the certification program administrator. This report may not be reproduced, except in full, without the approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC:

Audrey S. Matis Test Technician

Jody D. White Regional Manager

ASM:jdw/kmr Attachments (pages): Appendix-A: Weather Shield Windows & Doors Drawings (10). This report is complete only when all attachments listed are included.

Architectural Testing

Revision Log Rev. # 0

Date 03/01/05

Page(s) N/A

Revision (s) Original report issue

55828.02-602-44 Page 5 of 5