Architectural Testing

ANSI/AAMA/NWWDA 101/I.S. 2-97 TEST REPORT Rendered to: WEATHER SHIELD WINDOWS & DOORS SERIES/MODEL: Visions 2000 PRODUCT TYPE: Vinyl Sliding Glass Door (XO)

Title Rating Operating Force Air Infiltration Water Resistance Test Pressure Uniform Load Deflection Test Pressure Uniform Load Structural Test Pressure Forced Entry Resistance

Summary of Results SGD-R20 96x96 16 lbf max. 0.04 cfm/ft2 4.50 psf ±20.00 psf ±30.00 psf Grade 10

Reference should be made to Report No. 57593.01-602-44 for complete test specimen description and data.

5906 Saxon Avenue Schofield, WI 54476 phone: 715-241-8624 fax: 715-241-8425 www.archtest.com

Architectural Testing

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT Rendered to: Weather Shield Windows & Doors One Weather Shield Plaza Medford, WI 54451 Report No: 57593.01-602-44 Test Dates: 05/23/05 Through: 08/04/05 Report Date: 09/01/05 Expiration Date: 05/23/09 Project Summary: Architectural Testing, Inc was contracted by Weather Shield Windows & Doors, to perform testing on a Series/Model Visions 2000, Vinyl Sliding Glass Door (XO) at Architectural Testing, Inc test facility in Schofield, Wisconsin. The sample tested, successfully met the performance requirements for an SGD-R20 96x96 rating. Test specimen description and results are reported herein. Test Specifications: The test specimen was evaluated in accordance with the following: AAMA 1701.2-02, Voluntary Standard for Utilization in Manufactured Housing for Primary Windows and Sliding Glass Doors. ANSI/AAMA/NWWDA 101/I.S. 2-97, Voluntary Specifications for Aluminum, Vinyl (PVC) and Wood Windows and Glass Doors Test Specimen Description: Series/Model: Visions 2000 Product Type: Vinyl Sliding Glass Door (XO) Overall Size: 7' 11 -1/2" wide by 7' 11 -3/4" high Panel Size(s): 3' 11 -3/16" wide by 7' 9" high Screen Size: 4' -1/8" wide by 7' 9 -1/2" high Overall Area: 63.50 ft²

5906 Saxon Avenue Schofield, WI 54476 phone: 715-241-8624 fax: 715-241-8425 www.archtest.com

Architectural Testing

57593.01-602-44 Page 2 of 7

Test Specimen Description: (Continued) Finish: All vinyl was white. Glazing Details: Both panels utilized nominal 3/4" thick sealed insulating glass fabricated from two sheets of 5/32" thick clear tempered glass separated by 7/16" exposed corrugated aluminum spacer with butyl. The glass was set from the exterior against 1/8" glazing tape and a continuous backbed of silicone sealant. The exterior snap-fit vinyl glazing stops utilized on all four sides created the exterior seal. Weatherstripping: Description

Quantity

Location

0.187" backed by 0.280" high pile

1 Row

Frame perimeter

0.844" backed by 0.320" high pile by 0.810"wide dust plug

2

0.187" backed by 0.270" high pile w/center fin

1 Row

Active panel, exterior perimeter

0.187" backed by 0.280" high pile w/center fin

1 Row

Active and inactive panel meeting stiles

Interior panel at top and bottom of meeting stile

Frame and Panel Construction: The frame and panel members were mitered and employed welded corner construction. The frame utilized a snap-in interior vinyl track at the sill and also a snap-in vinyl screen track at the exterior sill. The inactive panel was set onto a continuous bed of sealant and secured to the frame at the head, jamb and sill with #8 by 2 -1/2" screws spaced approximately 24" on center. The active and inactive panels employed a snap-in vinyl interlock that was set in a bed of silicone sealant. Screen Construction: The screen frame consisted of extruded aluminum. The corners consisted of mitered, corner keyed and crimped construction. The screen utilized fiberglass mesh which was secured with a continuous rubber screen spline. Hardware: Description

Quantity

Location

Mortise lock and keeper

1

Locking stile/ frame 38 -3/4" from the sill

Operating handle

1

Locking stile, 39" from bottom of the active panel

57593.01-602-44 Page 3 of 7

Architectural Testing

Test Specimen Description: (Continued) Hardware: (Continued) Description

Quantity

Location

Tandem rollers

2

Bottom rail, active panel 2" from end

Sill track cap

1

Interior sill track

Door bumper

1

Interior sill track at inactive panel Stile

Drainage: Description

Quantity

Location

0.250" dia. hole

2

Exterior face of sill 1.500" from ends

0.500" by 0.187" slot

2

Frame sill, 1 -5/8" from jamb ends

Reinforcements: The meeting stiles were reinforced with hard wood (reference drawing 70-1892-01). The locking stile on the active panel was also reinforced with a galvanized formed steel channel (reference drawing P124000). The rails and inactive stile was reinforced with wood (reference drawing 70-0395-01). Installation: The window was installed into a nominal 2x12 wood buck. The interior side of the integral nailing flange was silicone sealed to the wood surround, as well as the fastener heads and secured with #8 by 1 -5/8" screws spaced approximately 12" on center. Test Results: The results are tabulated as follows: AAMA 1701.2-02 Paragraph

Title of Test - Test Method

2.2.3.1

Exterior Pressure per ASTM E 330-02 25.00 psf (positive) PASS

Results

Allowed No breakage or permanent set impairing operation

Architectural Testing

57593.01-602-44 Page 4 of 7

Test Results: (Continued) AAMA 1701.2-02 (Continued) Paragraph

Title of Test - Test Method

2.2.3.2

Interior Pressure per ASTM E 330-02 12.50 psf (negative) PASS

2.2.4

Air Infiltration per ASTM E 283-04 1.57 psf (25 mph) 0.04 cfm/ft²

0.50 cfm/ft² max.

Water Resistance per ASTM E 547-00 2.86 psf No leakage

No leakage

2.2.5

Results

Allowed No breakage or permanent set impairing operation

AAMA/NWWDA 101/I.S.2-97 Paragraph

Title of Test - Test Method

Results

Allowed

2.2.19.5.1

Operating Force

16 lbf

20 lbf max.

2.1.2

Air Infiltration per ASTM E 283-04 1.57 psf (25 mph) 0.04 cfm/ft2

See Note #1 0.3 cfm/ft2

Note #1: The tested specimen meets (or exceeds) the performance levels specified in ANSI/AAMA/NWWDA 101/I.S. 2-97 for air infiltration 2.1.3

Water Resistance per ASTM E 547-00

See Note #2

2.1.4.2

Uniform Load Structural per ASTM E 330-02

See Note #2

Note #2: The client opted to start at a pressure higher than the minimum required. Those results are listed under "Optional Performance.” 2.2.19.5.2

Deglazing Test per ASTM E 987-01 In operating direction at 70 lbs Left stile Meeting stile

0.060"/12% 0.060"/12%

0.500"/100% 0.500"/100%

0.020"/4% 0.015"/3%

0.500"/100% 0.500"/100%

In remaining direct at 50 lbs Top rail Bottom rail

Architectural Testing

57593.01-602-44 Page 5 of 7

Test Results: (Continued) Paragraph

Title of Test - Test Method

Results

Allowed

2.1.7

Welded Corner Test

Meets as stated

Meets as stated

2.1.8

Forced Entry Resistance per ASTM F 842-04 Type: A

Grade: 10

Disassembly Test

No entry

No entry

Tests A1 - A6

No entry

No entry

Hardware Manipulation Panel Manipulation Test

No entry No entry

No entry No entry

Optional Performance 4.3

4.4.2

Water Resistance per ASTM E 547-00 (with and without screen) 4.50 psf No leakage

No leakage

Uniform Load Structural per ASTM E 330-02 (Permanent sets reported were taken on the meeting stile) (Loads were held for 10 seconds) 30.00 psf (positive) 0.010" 0.372" max. 30.00 psf (negative) 0.020" 0.372" max.

Architectural Testing

57593.01-602-44 Page 6 of 7

Detailed drawings, representative samples of the test specimen and a copy of this report will be retained by Architectural Testing, Inc for a period of four years from the original test date. The above results were secured by using the designated test methods and they indicate compliance with the performance requirements of the above referenced specification. This report does not constitute certification of this product, which may only be granted by the certification program administrator. This report may not be reproduced, except in full, without the approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC

Audrey S. Matis Test Technician

Jody D. White Regional Manager

ASM:jdw/hlr Attachments (pages): Appendix-A: Drawings (23). This report is complete only when all attachments listed are included.

Architectural Testing

Revision Log Rev.# 0

Date 09/01/05

Page(s) N/A

Revision(s) Original report issue

57593.01-602-44 Page 7 of 7