OUTSIDE
OUTSIDE
Refer to Structural Engineer's drawings and specifications for all information on structural frame/ elements. Refer to Mechanical Engineer's drawings and specifications for all information on mechanical and electrical items.
Compriband 600 compressible sealant to fill gaps around window frame
215mm to slab edge
Sto through colour render system applied to blockwork, colour: White, installed in accordance with manufacturer's details and by approved contractor.
BBA approved DPC cavity tray fixed to insulation using fixing pins through fixing strip and jointing tape in accordance with manufacturer's requirements. System suitable for use with light gauge steel frame. Cavity tray to have pre-formed cloaks.
Compressible sealant to fill gaps around window frame
FFL Timber
SSL
panel size as shown on window type dwgs
Continuous horizontal cavity barrier at every separating floor such as Rockwool SP 60 to provide 60min fire rating and to prevent flanking sound. Slab cut on site to suit cavity width and fixed using proprietary fixing brackets to suit cavity. All to manufacturer's requirements. All gaps sealed with acoustic and intumescent sealant. *As shown on drawings 1310(AS)03/01-1310(AS)03/05.
Structural opening*
CL Curtain walling supports to manufacturers requirement
Lintel support to masonry skin to SE / manufacturers specification and design. Note: underside of lintel to have coloured finish: RAL 7015 Matt
EPDM to lap into structural opening to manufacturers details, PU expanding foam/ mineral wool insulation to fill gaps between fixings.
All cavity closers to be a Kingspan Thermabate, size to suit individual cavity.
Additional stud and brick-tie-channel to adjacent opening as SFS installer's details
Structural opening* BBA approved breather membrane lapped into window opening
Insulated cavity closer to fill cavity width, to provide thermal resistance of not less than 0.45m2K/W and to form integral DPC.
Insulated cavity closer to fill cavity width, to provide thermal resistance of not less than 0.45m2K/W and to form integral DPC.
Flexible sealant to fill gaps between dry lining and window frame
Flexible sealant to fill gaps between dry lining and window frame
AS BUILT Legend
B
PU expanding foam/ mineral wool insulation to fill gaps between fixing lugs
C D
A
TYPICAL HEAD / SEPARATING FLOOR DETAIL - BRICKWORK Compressible sealant to fill gaps around window frame Arbosil silicone seal to aluminium cill, sealant colour: Grey
Spandrel panel to RC slab edge, for sizes and locations refer to window types and window schedules 1310(AS)03/01-1310(AS)03-10.
CL
Un
ion
ad
Render / brickwork finish to window reveal, refer to elevation drawings 1310(GA)200-204
Pistol brick
Refer to drawings 1310(AS)07/-- and
*As shown 1310(AS)07/-on drawings 1310(AS)03/01 - 03/05
Ro
B1 UNIT - 1st FLOOR
TYPICAL JAMB DETAIL - RENDER
m
165mm to slab edge
INSIDE - B1UNIT 1st FLOOR
ha
50mm
Refer to drawing series 1310(AS)04/01
Ro
ad
Cl ap
Render thickness
Refer to drawing series 1310(AS)02/01
Refer to drawing 1310(AS)07/--
Structural opening*
TYPICAL HEAD DETAIL - RENDER
Specific Notes
Arbosil silicone seal to aluminium cill, sealant colour: Grey
BBA approved breather membrane lapped over DPC cavity tray
Flexible sealant to fill gaps between dry lining and window frame
All products are to be suitable for their purpose. The Contractor is to install all products where noted in accordance with manufacturers' recommendations/specifications and inform the Architect of any discrepancies or changes in the specification before proceeding with the work. This drawing is to be read in conjunction with all other relevant documentation including that produced by other consultants, subcontractors and suppliers.
PU expanding foam/ mineral wool insulation to fill gaps between fixings
10mm
EPDM to lap into structural opening to manufacturers details, PU expanding foam/ mineral wool insulation to fill gaps between fixings.
Continuous horizontal cavity barrier at every separating floor such as Rockwool SP 60 to provide 60min fire rating and to prevent flanking sound. Slab cut on site to suit cavity width and fixed using proprietary fixing brackets to suit cavity. All to manufacturer's requirements. All gaps sealed with acoustic and intumescent sealant.
10mm
Flexible sealant to fill gaps between dry lining and window frame
50mm
B1 UNIT - 1st FLOOR
Compressible sealant to fill gaps around window frame
OUTSIDE
Top of brick +15.300
Proprietary perpend weep holes at max. 1000mm c/c. colour to match mortar Min. 2no per openings
50mm
All drawings are indicative only. The sub-contractor is to submit shop drawings to the contract administrator of all the relevant components and elements for comment prior to fabrication.
Insulated cavity closer to fill cavity width, to provide thermal resistance of not less than 0.45m2K/W and to form integral DPC.
Render stop beads to manufacturer's details
Render thickness
All elements of work and materials are to comply with Building Regulations and British Standards, good industry practice and the recommendations of material and component manufacturers.
50mm
Insulated cavity closer to fill cavity width, to provide thermal resistance of not less than 0.45m2K/W and to form integral DPC.
BBA approved breather membrane lapped into window opening
35mm
BBA approved DPC cavity tray fixed to insulation using fixing pins through fixing strip and jointing tape in accordance with manufacturer's requirements. System suitable for use with light gauge steel frame. Cavity tray to have pre-formed cloaks.
IG Lintel support to masonry skin, specification to SE / manufacturers dwgs
Copyright Stephen Davy Peter Smith Architects 2013
All dimensions are given in millimetres, and internal dimensions are taken to face of blockwork. Do not scale from the drawing. All dimensions and conditions to be checked and confirmed on site by the Contractor. The Contractor should inform the Architect of any discrepancies before proceeding with the work.
Structural opening*
INSIDE RESIDENTIAL
Through colour render system applied to blockwork, colour: White, installed in accordance with manufacturer's details and by approved contractor.
C
35mm
BBA approved DPC cavity tray fixed to insulation using fixing pins through fixing strip and jointing tape in accordance with manufacturer's requirements. System suitable for use with light gauge steel frame. Cavity tray to have pre-formed cloaks.
Proprietary perpend weep holes at max. 1000mm c/c. colour to match mortar Min. 2no per openings Render angle beads and stop beads to manufacturer's details, render finish to window reveal
General Notes
Additional stud and brick-tie-channel to adjacent opening as SFS installer's details
BBA approved breather membrane lapped over DPC cavity tray
N
Key
Staffordshire smooth blue brick, 102.5mm thk stretcher bond facing brick wall with bucket handle joints
B1 UNIT GROUND FLOOR
TYPICAL JAMB DETAIL - BRICKWORK
TYPICAL FIRST FLOOR JUNCTION DETAIL - RENDER / BRICKWORK
OUTSIDE
Render thickness
50mm
Render / brickwork finish to window reveal, refer to elevation drawings 1310(GA)200-204 Curtain walling system to manufacturers recommendations, sizes and locations refer to window types and window schedules 1310(AS)03/01-1310(AS)03-10, Profile shown indicatively and structural support refer to manufactuer and SE details
165mm to slab edge
B1 UNIT GROUND FLOOR
30mins fire resistant partition
INSIDE REFUSE STORE
INSIDE - B1 UNIT Wall ties to SE specification
INSIDE - B1 UNIT (PROTECTED LOBBY)
35mm
Backing panel fixed behind spandrel panels, detail TBC with curtain walling manufacturer
SSL
-
Issued, As Built Cavity barrier added as clouded. Lintel amended to SE specification. Issued for construction. First Issue
Rev
Comment
PW 18.03.16 LN 09.12.13 TSo 23.08.13 TSo 24.07.13 By
Date
End of partition, specification TBC
stephen davy architects peter smith
Promatect non combustible material to junction, specification TBC
Fanshaw House, Fanshaw Street, London N1 6HX Tel: 020 7739 2020 Fax: 020 7739 2021 E-mail:
[email protected] Website: www.davysmitharchitects.co.uk
FFL Timber
PPC aluminium cill profile with drip detail, colour: RAL 7015 Matt (Slate Grey) Render stop beads to manufacturer's details, render finish to window reveal
INSIDE - B1 UNIT
C B A
DPC to lap into curtain walling Insulated cavity closer to fill cavity width, to provide thermal resistance of not less than 0.45m2K/W and to form integral DPC.
Curtain walling system with integrated entrance doorset
Curtain walling supports to manufacturers requirement
4 Elstree Gate Elstree Way Borehamwood Hertfordshire WD6 1JD
Continuous horizontal cavity barrier at every separating floor such as Rockwool SP 60 to provide 60min fire rating and to prevent flanking sound. Slab cut on site to suit cavity width and fixed using proprietary fixing brackets to suit cavity. All to manufacturer's requirements. All gaps sealed with acoustic and intumescent sealant.
01 1310(AS)03-13
TYPICAL GROUND FLOOR CILL DETAIL - RENDER
Structural opening*
Project
B1 UNIT BASEMENT
Head Detail
Client
Continuous vertical cavity barrier with DPC to provide 60min fire rating and to prevent flanking sound. Installed to manufacturer's requirements
Union Road Union Road / Clapham Road Clapham SW4
Spandrel panel to RC slab edge, for sizes and locations refer to window types and window schedules 1310(AS)03/01-1310(AS)03-10.
Drawing Title
OUTSIDE Job No.
Drawn By
Scale
1310
TSo
1:5 @ A1
Date
Checked By
July 2013
TSo/KK
Drawing No.
TYPICAL JUNCTION DETAIL - SEPARATING WALL
TYPICAL JUNCTION DETAIL - PARTITION
1310(AS)03/13
Revision
C