OUTSIDE

OUTSIDE

Refer to Structural Engineer's drawings and specifications for all information on structural frame/ elements. Refer to Mechanical Engineer's drawings and specifications for all information on mechanical and electrical items.

Compriband 600 compressible sealant to fill gaps around window frame

215mm to slab edge

Sto through colour render system applied to blockwork, colour: White, installed in accordance with manufacturer's details and by approved contractor.

BBA approved DPC cavity tray fixed to insulation using fixing pins through fixing strip and jointing tape in accordance with manufacturer's requirements. System suitable for use with light gauge steel frame. Cavity tray to have pre-formed cloaks.

Compressible sealant to fill gaps around window frame

FFL Timber

SSL

panel size as shown on window type dwgs

Continuous horizontal cavity barrier at every separating floor such as Rockwool SP 60 to provide 60min fire rating and to prevent flanking sound. Slab cut on site to suit cavity width and fixed using proprietary fixing brackets to suit cavity. All to manufacturer's requirements. All gaps sealed with acoustic and intumescent sealant. *As shown on drawings 1310(AS)03/01-1310(AS)03/05.

Structural opening*

CL Curtain walling supports to manufacturers requirement

Lintel support to masonry skin to SE / manufacturers specification and design. Note: underside of lintel to have coloured finish: RAL 7015 Matt

EPDM to lap into structural opening to manufacturers details, PU expanding foam/ mineral wool insulation to fill gaps between fixings.

All cavity closers to be a Kingspan Thermabate, size to suit individual cavity.

Additional stud and brick-tie-channel to adjacent opening as SFS installer's details

Structural opening* BBA approved breather membrane lapped into window opening

Insulated cavity closer to fill cavity width, to provide thermal resistance of not less than 0.45m2K/W and to form integral DPC.

Insulated cavity closer to fill cavity width, to provide thermal resistance of not less than 0.45m2K/W and to form integral DPC.

Flexible sealant to fill gaps between dry lining and window frame

Flexible sealant to fill gaps between dry lining and window frame

AS BUILT Legend

B

PU expanding foam/ mineral wool insulation to fill gaps between fixing lugs

C D

A

TYPICAL HEAD / SEPARATING FLOOR DETAIL - BRICKWORK Compressible sealant to fill gaps around window frame Arbosil silicone seal to aluminium cill, sealant colour: Grey

Spandrel panel to RC slab edge, for sizes and locations refer to window types and window schedules 1310(AS)03/01-1310(AS)03-10.

CL

Un

ion

ad

Render / brickwork finish to window reveal, refer to elevation drawings 1310(GA)200-204

Pistol brick

Refer to drawings 1310(AS)07/-- and

*As shown 1310(AS)07/-on drawings 1310(AS)03/01 - 03/05

Ro

B1 UNIT - 1st FLOOR

TYPICAL JAMB DETAIL - RENDER

m

165mm to slab edge

INSIDE - B1UNIT 1st FLOOR

ha

50mm

Refer to drawing series 1310(AS)04/01

Ro

ad

Cl ap

Render thickness

Refer to drawing series 1310(AS)02/01

Refer to drawing 1310(AS)07/--

Structural opening*

TYPICAL HEAD DETAIL - RENDER

Specific Notes

Arbosil silicone seal to aluminium cill, sealant colour: Grey

BBA approved breather membrane lapped over DPC cavity tray

Flexible sealant to fill gaps between dry lining and window frame

All products are to be suitable for their purpose. The Contractor is to install all products where noted in accordance with manufacturers' recommendations/specifications and inform the Architect of any discrepancies or changes in the specification before proceeding with the work. This drawing is to be read in conjunction with all other relevant documentation including that produced by other consultants, subcontractors and suppliers.

PU expanding foam/ mineral wool insulation to fill gaps between fixings

10mm

EPDM to lap into structural opening to manufacturers details, PU expanding foam/ mineral wool insulation to fill gaps between fixings.

Continuous horizontal cavity barrier at every separating floor such as Rockwool SP 60 to provide 60min fire rating and to prevent flanking sound. Slab cut on site to suit cavity width and fixed using proprietary fixing brackets to suit cavity. All to manufacturer's requirements. All gaps sealed with acoustic and intumescent sealant.

10mm

Flexible sealant to fill gaps between dry lining and window frame

50mm

B1 UNIT - 1st FLOOR

Compressible sealant to fill gaps around window frame

OUTSIDE

Top of brick +15.300

Proprietary perpend weep holes at max. 1000mm c/c. colour to match mortar Min. 2no per openings

50mm

All drawings are indicative only. The sub-contractor is to submit shop drawings to the contract administrator of all the relevant components and elements for comment prior to fabrication.

Insulated cavity closer to fill cavity width, to provide thermal resistance of not less than 0.45m2K/W and to form integral DPC.

Render stop beads to manufacturer's details

Render thickness

All elements of work and materials are to comply with Building Regulations and British Standards, good industry practice and the recommendations of material and component manufacturers.

50mm

Insulated cavity closer to fill cavity width, to provide thermal resistance of not less than 0.45m2K/W and to form integral DPC.

BBA approved breather membrane lapped into window opening

35mm

BBA approved DPC cavity tray fixed to insulation using fixing pins through fixing strip and jointing tape in accordance with manufacturer's requirements. System suitable for use with light gauge steel frame. Cavity tray to have pre-formed cloaks.

IG Lintel support to masonry skin, specification to SE / manufacturers dwgs

Copyright Stephen Davy Peter Smith Architects 2013

All dimensions are given in millimetres, and internal dimensions are taken to face of blockwork. Do not scale from the drawing. All dimensions and conditions to be checked and confirmed on site by the Contractor. The Contractor should inform the Architect of any discrepancies before proceeding with the work.

Structural opening*

INSIDE RESIDENTIAL

Through colour render system applied to blockwork, colour: White, installed in accordance with manufacturer's details and by approved contractor.

C

35mm

BBA approved DPC cavity tray fixed to insulation using fixing pins through fixing strip and jointing tape in accordance with manufacturer's requirements. System suitable for use with light gauge steel frame. Cavity tray to have pre-formed cloaks.

Proprietary perpend weep holes at max. 1000mm c/c. colour to match mortar Min. 2no per openings Render angle beads and stop beads to manufacturer's details, render finish to window reveal

General Notes

Additional stud and brick-tie-channel to adjacent opening as SFS installer's details

BBA approved breather membrane lapped over DPC cavity tray

N

Key

Staffordshire smooth blue brick, 102.5mm thk stretcher bond facing brick wall with bucket handle joints

B1 UNIT GROUND FLOOR

TYPICAL JAMB DETAIL - BRICKWORK

TYPICAL FIRST FLOOR JUNCTION DETAIL - RENDER / BRICKWORK

OUTSIDE

Render thickness

50mm

Render / brickwork finish to window reveal, refer to elevation drawings 1310(GA)200-204 Curtain walling system to manufacturers recommendations, sizes and locations refer to window types and window schedules 1310(AS)03/01-1310(AS)03-10, Profile shown indicatively and structural support refer to manufactuer and SE details

165mm to slab edge

B1 UNIT GROUND FLOOR

30mins fire resistant partition

INSIDE REFUSE STORE

INSIDE - B1 UNIT Wall ties to SE specification

INSIDE - B1 UNIT (PROTECTED LOBBY)

35mm

Backing panel fixed behind spandrel panels, detail TBC with curtain walling manufacturer

SSL

-

Issued, As Built Cavity barrier added as clouded. Lintel amended to SE specification. Issued for construction. First Issue

Rev

Comment

PW 18.03.16 LN 09.12.13 TSo 23.08.13 TSo 24.07.13 By

Date

End of partition, specification TBC

stephen davy architects peter smith

Promatect non combustible material to junction, specification TBC

Fanshaw House, Fanshaw Street, London N1 6HX Tel: 020 7739 2020 Fax: 020 7739 2021 E-mail: [email protected] Website: www.davysmitharchitects.co.uk

FFL Timber

PPC aluminium cill profile with drip detail, colour: RAL 7015 Matt (Slate Grey) Render stop beads to manufacturer's details, render finish to window reveal

INSIDE - B1 UNIT

C B A

DPC to lap into curtain walling Insulated cavity closer to fill cavity width, to provide thermal resistance of not less than 0.45m2K/W and to form integral DPC.

Curtain walling system with integrated entrance doorset

Curtain walling supports to manufacturers requirement

4 Elstree Gate Elstree Way Borehamwood Hertfordshire WD6 1JD

Continuous horizontal cavity barrier at every separating floor such as Rockwool SP 60 to provide 60min fire rating and to prevent flanking sound. Slab cut on site to suit cavity width and fixed using proprietary fixing brackets to suit cavity. All to manufacturer's requirements. All gaps sealed with acoustic and intumescent sealant.

01 1310(AS)03-13

TYPICAL GROUND FLOOR CILL DETAIL - RENDER

Structural opening*

Project

B1 UNIT BASEMENT

Head Detail

Client

Continuous vertical cavity barrier with DPC to provide 60min fire rating and to prevent flanking sound. Installed to manufacturer's requirements

Union Road Union Road / Clapham Road Clapham SW4

Spandrel panel to RC slab edge, for sizes and locations refer to window types and window schedules 1310(AS)03/01-1310(AS)03-10.

Drawing Title

OUTSIDE Job No.

Drawn By

Scale

1310

TSo

1:5 @ A1

Date

Checked By

July 2013

TSo/KK

Drawing No.

TYPICAL JUNCTION DETAIL - SEPARATING WALL

TYPICAL JUNCTION DETAIL - PARTITION

1310(AS)03/13

Revision

C